Failed: Building - Final
M1503.1general.
range Hoods Shall Discharge To The Outdoors Through A Duct. The Duct Serving The Hood Shall Have A Smooth Interior Surface, Shall Be Air Tight, Shall Be Equipped With A Back-draft Damper And Shall Be Independent Of All Other Exhaust Systems. Ducts Serving Range Hoods Shall Not Terminate In An Attic Or Crawl Space Or Areas Inside The Building.
exception: Where Installed In Accordance With The Manufacturer’s Instructions, And Where Mechanical Or Natural Ventilation Is Otherwise Provided, Listed And Labeled Ductless Range Hoods Shall Not Be Required To Discharge To The Outdoors.
m1305.1.4.1ground Clearance.
equipment And Appliances Supported From The Ground Shall Be Level And Firmly Supported On A Concrete Slab Or Other Approved Material Extending Not Less Than 3 Inches (76 Mm) Above The Adjoining Ground. Such Support Shall Be In Accordance With The Manufacturer’s Installation Instructions. Appliances Suspended From The Floor Shall Have A Clearance Of Not Less Than 6 Inches (152 Mm) From The Ground.
r318.5protection Against Decay And Termites.
condensate Lines, Irrigation/sprinkler System Risers For Spray Heads, And Roof Downspouts Shall Discharge At Least 1 Foot (305 Mm) Away From The Structure Sidewall, Whether By Underground Piping, Tail Extensions Or Splash Blocks. Gutters With Downspouts Are Required On All Buildings With Eaves Of Less Than 6 Inches (152 Mm) Horizontal Projection Except For Gable End Rakes Or On A Roof Above Another Roof.
Inspected by Anthony Aslan