Columbia County is committed to ensuring accessibility to this website regardless of disability. If anyone encounters a feature on this website that is inaccessible due to a disability, please contact the County Manger’s Office and the Columbia County Board of County Commissioners at (386) 758-1005. You may also email that office at patrick_weaver@columbiacountyfla.com and provide a brief description of the inaccessible feature. The County will either correct the inaccessible feature or, if correction is not possible due to technical limitations, provide the desired information through alternative means.

Skip to content

Columbia County, FL | Permit Details

New Residential Construction Permit
Address 414 SW ROSEMARY DR
LAKE CITY, FL 32024
Parcel #: 02731-003
Acres: 0.26
Owner: The Preserve At Laurel Lakes Inc
Subdivision: Preserve At Laurel Lake Unit 1
Zoning: PRD
Flood Zone: X
District: 3
Application #: 47946
Permit #: 000041308
Related Permit: Culvert Waiver: 000041309
Submitted: Wednesday, November 24, 2021
Issued: Thursday, February 11, 2021
Expires: Wednesday, January 12, 2022
Completed: Wednesday, January 12, 2022
Status: Completed
Septic Release? Yes
Notes:
ELEVATION CONFIRMATION LETTER REC'D @ 116.5'
Job Details
This is the construction of a Single Family Dwelling
Heated Area (Sqft) 1995.9
Total Area (Sqft) 2866
Stories 1
Building Height 22
Building Code Construction Type V
Building Code Element B
Building Code Occupancy Types Residential
Occupancy Use Title single family dwelling
Setbacks Front 25
Setback Side 1 10
Setback Side 2 10
Setbacks Rear 15
Septic# (00-0000) or (X00-000) x-city
Building Code Edition Florida Building Code 2017 6th Edition & 2014 National Electrical Code
Elevation regulation Subdivision Plat
Finished floor requirement 115.9
Requirement needed By Nailing Inspection
Document needed is a Surveyor letter giving the Finished Floor Elevation
Document receieved Yes
Fema map number 12023C0290D
In floodway N
Review Notes
12/9/2020 Point Review - Received-Hard Copy Application
12/9/2020 Point Review - Reviewed
12/10/2020 Zoning Review - Reviewed
12/15/2020 Plan Review - Documents Required
1/11/2021 Plan Review - Documents Required
2/1/2021 Plan Review - Reviewed NEEDED: SOIL REPORT AND OR SPECIAL FOUNDATION NEEDED RECEIVED 1-29-21
2/4/2021 Zoning Review - Reviewed NEEDED: SOIL REPORT AND OR SPECIAL FOUNDATION NEEDED RECEIVED 1-29-21
2/4/2021 Final Review - Reviewed NEEDED: SOIL REPORT AND OR SPECIAL FOUNDATION NEEDED RECEIVED 1-29-21
2/10/2021 Final Review - Payment Needed NEEDED: SOIL REPORT AND OR SPECIAL FOUNDATION NEEDED RECEIVED 1-29-21
2/11/2021 Permit Issued Permit #000041308 created and approved.
10/12/2021 Final Review - Payment Needed NEEDED: SOIL REPORT AND OR SPECIAL FOUNDATION NEEDED RECEIVED 1-29-21
10/12/2021 Final Review - Payment Needed NEEDED: SOIL REPORT AND OR SPECIAL FOUNDATION NEEDED RECEIVED 1-29-21
11/24/2021 Final Review - Payment Needed NEEDED: SOIL REPORT AND OR SPECIAL FOUNDATION NEEDED RECEIVED 1-29-21
Contractors
Name/ Business License Title Role
Aaron Simque
Aaron Simque Homes Inc
County License & State License Expired.
RR282811879 Residential Contractor Contractor
Stephen M Brisbois
Epic Ac Service
Workers Comp Expired.
CAC1819412 Cert. A/c Class “b” Subcontractor
Ryan C Beville
Rbi Electrical Contracting Llc
EC13004236 Electrical Contractor Subcontractor
Ralph W Laverdure
Rwl Roofing,llc.
CCC1328590 Roofing Contractor Subcontractor
Billy B Rathel Jr
Five Star Plumbing Big Bend, Inc.
CFC1427547 Cert. Plumbing Subcontractor
Inspections
Inspection Notes Performed By Date
Passed: Building - Footer Troy Crews 3/10/2021
Passed: Engineering - Setbacks Troy Crews 3/10/2021
Passed: Plumbing/Gas - 1st Underground Rough–In Waste Only Remainder Of Water Overhead ? Troy Crews 4/12/2021
Passed: Building - Slab Troy Crews 4/21/2021
Passed: Building - Roof Decking Troy Crews 5/27/2021
Passed: Building - Wall Sheathing Do Not Cover Post Until Strapping Inspected, No Further Inspections Until Elevation Certified Troy Crews 5/27/2021
Failed: Building - Framing To1 Truss Has 3336 Uplift Midspan Missing Screws Or Strapping Matt Forsyth 6/23/2021
Passed: Electrical - 2nd Rough-In Matt Forsyth 6/23/2021
Passed: Mechanical - Rough In Matt Forsyth 6/23/2021
Passed: Building - Framing Matt Forsyth 7/21/2021
Passed: Electrical - 2nd Rough-In Matt Forsyth 7/21/2021
Failed: Mechanical - Rough In Dryer Duct Shall Have No Screws. Dryer Duct Cannot Be Installed With Deformation.m1502.4.2 Matt Forsyth 7/21/2021
Failed: Plumbing/Gas - 2nd Rough-In Nail Plates Needed For Water Line At Top Of Wall In Two Places Matt Forsyth 7/21/2021
Passed: Plumbing/Gas - Tub Set/Shower Pan Matt Forsyth 7/21/2021
Failed: Building - Insulation Enclosed Garage Not On Plans Need Revision, Also Not Insulated And Has Ac Ducts, Do Not Sheetrock Garage Until Changes Approved And Insulated Troy Crews 7/29/2021
Passed: Electrical - Permanent Power Troy Crews 10/13/2021
Release to power company Troy Crews 10/13/2021
Failed: Building - Final Water Heater Needs To Be Wired, Open Ducts In Garage Not Properly Sealed For Conditioned Space, Need Blower Door Test. Troy Crews 1/11/2022
Certificate-Release Certificate Troy Crews 1/12/2022
Passed: Building - Final Need Blower Door Test Troy Crews 1/12/2022