Columbia County is committed to ensuring accessibility to this website regardless of disability. If anyone encounters a feature on this website that is inaccessible due to a disability, please contact the County Manger’s Office and the Columbia County Board of County Commissioners at (386) 758-1005. You may also email that office at patrick_weaver@columbiacountyfla.com and provide a brief description of the inaccessible feature. The County will either correct the inaccessible feature or, if correction is not possible due to technical limitations, provide the desired information through alternative means.

Skip to content

Columbia County, FL | Permit Details

Generator Permit

Address 1634 SW SUNVIEW ST
FORT WHITE, FL 32038
Parcel #: 03745-214
Acres: 5.00
Owner: Hall Deborah E
Subdivision: Sunview Estates
Zoning: ESA-2
Flood Zone: X
District: 2
Application #: 74326
Permit #: 000054555
Related Permit:
Submitted: Thursday, November 20, 2025
Issued: Friday, November 21, 2025
Expires: Friday, December 19, 2025
Completed: Friday, December 19, 2025
Status: Completed
Septic Release? Yes
Notes:

Job Details
Finished floor requirement
Fema map number 12023C0390C
Residential or Commercial? Residential
What is the power service for? Existing Site Built Home
Number of requested AMPS for electrical service: 200
Septic # (00-0000) or (X00-000) x25
Electrical Code Edition 2020 National Electrical Code
Review Notes
11/20/2025 Application pending.
11/20/2025 Application submitted by applicant.
11/21/2025 Application Status Update Notification
11/21/2025 Permit Issued
Contractors
Name/ Business License Title Role
Jack E Phillips
Security Safe Company
EC13014598 Cert. Electrical Contractor
Inspections
Inspection Notes Performed By Date
Failed: Electrical - Generator Final 1. All Aluminum Wires Require Anti-oxidant Compound On The Exposed Portion Of Cable After The Removal Of Insulation And Before The Wire Is Installed In The Termination Lugs Of Panels. Some Of The Wiring Involved In This Installation Has No Anti-oxidant Compound And Some Only Have The Compound Spread On Top Of The Lugs, 2. All Unused Openings Including The Dead Front Of Equipment Required Closers, 3. All Wiring Associated With The Installation Shall Be Behind The Dead Front So As Not To Be Using Any Part Of The Dead Front To Hold Wires Into Boxes. Please Reschedule Inspection After Defects Have Been Completed And Let The Home Owner Know The Date We Are To Arrive For Inspection Gary Pitzer 12/17/2025
Passed: Electrical - Generator Final No Gas Inspection Gary Pitzer 12/19/2025
Release to power company Gary Pitzer 12/19/2025