Generator
Permit
| Application #: | 74326 |
| Permit #: |
000054555 |
| Related Permit: |
|
| Submitted: | Thursday, November 20, 2025 |
| Issued: | Friday, November 21, 2025 |
| Expires: | Friday, December 19, 2025 |
| Completed: | Friday, December 19, 2025 |
| Status: |
Completed |
| Septic Release? |
Yes |
Job Details
| Finished floor requirement |
|
| Fema map number |
12023C0390C |
| Residential or Commercial? |
Residential |
| What is the power service for? |
Existing Site Built Home |
| Number of requested AMPS for electrical service: |
200 |
| Septic # (00-0000) or (X00-000) |
x25 |
| Electrical Code Edition |
2020 National Electrical Code |
Review Notes
| 11/20/2025 |
Application pending. |
| 11/20/2025 |
Application submitted by applicant. |
| 11/21/2025 |
Application Status Update Notification |
| 11/21/2025 |
Permit Issued |
Contractors
| Name / Business |
License |
Title |
Role |
Jack E Phillips Security Safe Company
Workers Comp Expired. |
EC13014598 |
Cert. Electrical |
Contractor |
Inspections
| Inspection |
Notes |
Performed By |
Date |
| Failed: Electrical - Generator Final |
1. All Aluminum Wires Require Anti-oxidant Compound On The Exposed Portion Of Cable After The Removal Of Insulation And Before The Wire Is Installed In The Termination Lugs Of Panels. Some Of The Wiring Involved In This Installation Has No Anti-oxidant Compound And Some Only Have The Compound Spread On Top Of The Lugs, 2. All Unused Openings Including The Dead Front Of Equipment Required Closers, 3. All Wiring Associated With The Installation Shall Be Behind The Dead Front So As Not To Be Using Any Part Of The Dead Front To Hold Wires Into Boxes. Please Reschedule Inspection After Defects Have Been Completed And Let The Home Owner Know The Date We Are To Arrive For Inspection |
Gary Pitzer |
12/17/2025 |
| Passed: Electrical - Generator Final |
No Gas Inspection |
Gary Pitzer |
12/19/2025 |
| Release to power company |
|
Gary Pitzer |
12/19/2025 |