Generator
Permit
| Application #: | 70248 |
| Permit #: |
000052822 |
| Related Permit: |
|
| Submitted: | Thursday, April 3, 2025 |
| Issued: | Thursday, April 3, 2025 |
| Expires: | Wednesday, April 16, 2025 |
| Completed: | Wednesday, April 16, 2025 |
| Status: |
Completed |
| Septic Release? |
Yes |
Job Details
| Finished floor requirement |
|
| Fema map number |
12023C0395C |
| Residential or Commercial? |
Residential |
| What is the power service for? |
Existing Site Built Home |
| Number of requested AMPS for electrical service: |
200 |
| Septic # (00-0000) or (X00-000) |
x25 |
| Electrical Code Edition |
2020 National Electrical Code |
Review Notes
| 4/3/2025 |
Application pending. |
| 4/3/2025 |
Application submitted by applicant. |
| 4/3/2025 |
Permit Issued |
Contractors
| Name / Business |
License |
Title |
Role |
Jack E Phillips Security Safe Company
Workers Comp Expired. |
EC13014598 |
Cert. Electrical |
Contractor |
Inspections
| Inspection |
Notes |
Performed By |
Date |
| Failed: Electrical - Generator Final |
The Grounded Conductors (neutrals) Shall Terminate In The First Means Of Disconnect. The First Means Of Disconnect Is Where All Bonding Is To Completed With The Grounded Conductors. At This Service Your First Means Of Disconnect Is Your Transfer Switch. |
Gary Pitzer |
4/15/2025 |
| Rescheduled 4/16/2025:Electrical - Service Upgrade Final |
|
Emaleigh Williams |
4/16/2025 |
| Passed: Electrical - Service Upgrade Final |
Defects Corrected |
Gary Pitzer |
4/16/2025 |
| Release to power company |
|
Gary Pitzer |
4/16/2025 |