5/13/2024
|
Application pending.
|
5/23/2024
|
Application submitted by applicant.
|
5/23/2024
|
Point Review - Printed-Online Application
NEEDED:
*COMPLETE APPLICANT ADDRESS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
*SEALED BUILDING PLANS
****STAFF***
NEEDS DEVELOPMENT PERMIT # AND FEE
|
5/23/2024
|
Point Review - Reviewed
NEEDED:
*COMPLETE APPLICANT ADDRESS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
*SEALED BUILDING PLANS
****STAFF***
NEEDS DEVELOPMENT PERMIT # AND FEE
|
5/24/2024
|
Zoning Review - Reviewed
NEEDED:
*COMPLETE APPLICANT ADDRESS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
*SEALED BUILDING PLANS
ZONING: BFE OF 35FT. DFE OF 36FT.
*ELECTRIC SHALL BE WATERPROOFED TO DFE.
*ENGINEERED OR NON-ENGINEERED FLOOD OPENINGS MUST BE NOTED ON THE BUILDING PLANS WITH LOCATION AND SIZE/FLOW CALCULATIONS AND LOCATION NO HIGHER THAT 12" ABOVE ADJACENT FINISHED GRADE. IF USING ENGINEERED VENTS, PROVIDE INFORMATION OF VENTS.
*FINAL ELEVATION CERTIFICATE IS REQUIRED TO DOCUMENT VENTS AND ELEVATION.
****STAFF***
NEEDS DEVELOPMENT PERMIT # AND FEE
|
5/28/2024
|
Plan Review - Documents Required
NEEDED:
*COMPLETE APPLICANT ADDRESS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
*SEALED BUILDING PLANS
ZONING: BFE OF 35FT. DFE OF 36FT.
*ELECTRIC SHALL BE WATERPROOFED TO DFE.
*ENGINEERED OR NON-ENGINEERED FLOOD OPENINGS MUST BE NOTED ON THE BUILDING PLANS WITH LOCATION AND SIZE/FLOW CALCULATIONS AND LOCATION NO HIGHER THAT 12" ABOVE ADJACENT FINISHED GRADE. IF USING ENGINEERED VENTS, PROVIDE INFORMATION OF VENTS.
*FINAL ELEVATION CERTIFICATE IS REQUIRED TO DOCUMENT VENTS AND ELEVATION.
****STAFF***
NEEDS DEVELOPMENT PERMIT # AND FEE
|
5/31/2024
|
Zoning Review - Reviewed
NEEDED:
*COMPLETE APPLICANT ADDRESS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
*SEALED BUILDING PLANS
ZONING: BFE OF 35FT. DFE OF 36FT.
*ELECTRIC SHALL BE WATERPROOFED TO DFE.
*ENGINEERED OR NON-ENGINEERED FLOOD OPENINGS MUST BE NOTED ON THE BUILDING PLANS WITH LOCATION AND SIZE/FLOW CALCULATIONS AND LOCATION NO HIGHER THAT 12" ABOVE ADJACENT FINISHED GRADE. IF USING ENGINEERED VENTS, PROVIDE INFORMATION OF VENTS.
*FINAL ELEVATION CERTIFICATE REQUIRED PRIOR TO FINAL INSPECTION.
****STAFF***
NEEDS DEVELOPMENT PERMIT # AND FEE
|
6/3/2024
|
Plan Review - On Hold-Incomplete
NEEDED:
*COMPLETE APPLICANT ADDRESS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
*SEALED BUILDING PLANS
ZONING: BFE OF 35FT. DFE OF 36FT.
*ELECTRIC SHALL BE WATERPROOFED TO DFE.
*ENGINEERED OR NON-ENGINEERED FLOOD OPENINGS MUST BE NOTED ON THE BUILDING PLANS WITH LOCATION AND SIZE/FLOW CALCULATIONS AND LOCATION NO HIGHER THAT 12" ABOVE ADJACENT FINISHED GRADE. IF USING ENGINEERED VENTS, PROVIDE INFORMATION OF VENTS.
*FINAL ELEVATION CERTIFICATE REQUIRED PRIOR TO FINAL INSPECTION.
****STAFF***
NEEDS DEVELOPMENT PERMIT # AND FEE
|
6/11/2024
|
Plan Review - On Hold-Incomplete
NEEDED:
*COMPLETE APPLICANT ADDRESS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
*SEALED BUILDING PLANS
ZONING: ACCESSORY BUILDING. EC
*ELECTRIC SHALL BE WATERPROOFED TO DFE.
*ENGINEERED OR NON-ENGINEERED FLOOD OPENINGS MUST BE NOTED ON THE BUILDING PLANS WITH LOCATION AND SIZE/FLOW CALCULATIONS AND LOCATION NO HIGHER THAT 12" ABOVE ADJACENT FINISHED GRADE. IF USING ENGINEERED VENTS, PROVIDE INFORMATION OF VENTS.
*FINAL ELEVATION CERTIFICATE REQUIRED PRIOR TO FINAL INSPECTION.
****STAFF***
NEEDS DEVELOPMENT PERMIT # AND FEE
|
6/18/2024
|
Plan Review - On Hold-Incomplete
NEEDED:
*COMPLETE APPLICANT ADDRESS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
*SEALED BUILDING PLANS
ZONING: ACCESSORY BUILDING. EC
*ELECTRIC SHALL BE WATERPROOFED TO DFE.
*ENGINEERED OR NON-ENGINEERED FLOOD OPENINGS MUST BE NOTED ON THE BUILDING PLANS WITH LOCATION AND SIZE/FLOW CALCULATIONS AND LOCATION NO HIGHER THAT 12" ABOVE ADJACENT FINISHED GRADE. IF USING ENGINEERED VENTS, PROVIDE INFORMATION OF VENTS.
*FINAL ELEVATION CERTIFICATE REQUIRED PRIOR TO FINAL INSPECTION.
****STAFF***
NEEDS DEVELOPMENT PERMIT # AND FEE
|
6/24/2024
|
Plan Review - On Hold-Incomplete
NEEDED:
*COMPLETE APPLICANT ADDRESS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
*SEALED BUILDING PLANS
ZONING: ACCESSORY BUILDING. EC
*ELECTRIC SHALL BE WATERPROOFED TO DFE.
*ENGINEERED OR NON-ENGINEERED FLOOD OPENINGS MUST BE NOTED ON THE BUILDING PLANS WITH LOCATION AND SIZE/FLOW CALCULATIONS AND LOCATION NO HIGHER THAT 12" ABOVE ADJACENT FINISHED GRADE. IF USING ENGINEERED VENTS, PROVIDE INFORMATION OF VENTS.
*FINAL ELEVATION CERTIFICATE REQUIRED PRIOR TO FINAL INSPECTION.
****STAFF***
NEEDS DEVELOPMENT PERMIT # AND FEE
|
7/1/2024
|
Plan Review - On Hold-Incomplete
NEEDED:
*COMPLETE APPLICANT ADDRESS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
*SEALED BUILDING PLANS
ZONING: ACCESSORY BUILDING. EC
*ELECTRIC SHALL BE WATERPROOFED TO DFE.
*ENGINEERED OR NON-ENGINEERED FLOOD OPENINGS MUST BE NOTED ON THE BUILDING PLANS WITH LOCATION AND SIZE/FLOW CALCULATIONS AND LOCATION NO HIGHER THAT 12" ABOVE ADJACENT FINISHED GRADE. IF USING ENGINEERED VENTS, PROVIDE INFORMATION OF VENTS.
*FINAL ELEVATION CERTIFICATE REQUIRED PRIOR TO FINAL INSPECTION.
****STAFF***
NEEDS DEVELOPMENT PERMIT # AND FEE
|
7/9/2024
|
Plan Review - On Hold-Incomplete
NEEDED:
*COMPLETE APPLICANT ADDRESS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
*SEALED BUILDING PLANS
ZONING: ACCESSORY BUILDING. EC
*ELECTRIC SHALL BE WATERPROOFED TO DFE.
*ENGINEERED OR NON-ENGINEERED FLOOD OPENINGS MUST BE NOTED ON THE BUILDING PLANS WITH LOCATION AND SIZE/FLOW CALCULATIONS AND LOCATION NO HIGHER THAT 12" ABOVE ADJACENT FINISHED GRADE. IF USING ENGINEERED VENTS, PROVIDE INFORMATION OF VENTS.
*FINAL ELEVATION CERTIFICATE REQUIRED PRIOR TO FINAL INSPECTION.
****STAFF***
NEEDS DEVELOPMENT PERMIT # AND FEE
|
7/15/2024
|
Plan Review - Reviewed
NEEDED:
*COMPLETE APPLICANT ADDRESS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
ZONING: ACCESSORY BUILDING. EC
*ELECTRIC SHALL BE WATERPROOFED TO DFE.
*ENGINEERED OR NON-ENGINEERED FLOOD OPENINGS MUST BE NOTED ON THE BUILDING PLANS WITH LOCATION AND SIZE/FLOW CALCULATIONS AND LOCATION NO HIGHER THAT 12" ABOVE ADJACENT FINISHED GRADE. IF USING ENGINEERED VENTS, PROVIDE INFORMATION OF VENTS.
*FINAL ELEVATION CERTIFICATE REQUIRED PRIOR TO FINAL INSPECTION.
****STAFF***
NEEDS DEVELOPMENT PERMIT # AND FEE
|
7/22/2024
|
Plan Review - Documents Required
ZONING: ACCESSORY BUILDING. EC
*ELECTRIC SHALL BE WATERPROOFED TO DFE.
*ENGINEERED OR NON-ENGINEERED FLOOD OPENINGS MUST BE NOTED ON THE BUILDING PLANS WITH LOCATION AND SIZE/FLOW CALCULATIONS AND LOCATION NO HIGHER THAT 12" ABOVE ADJACENT FINISHED GRADE. IF USING ENGINEERED VENTS, PROVIDE INFORMATION OF VENTS.
*FINAL ELEVATION CERTIFICATE REQUIRED PRIOR TO FINAL INSPECTION.
****STAFF***
NEEDS DEVELOPMENT PERMIT # AND FEE
|
7/22/2024
|
Plan Review - Reviewed
ZONING: ACCESSORY BUILDING. EC
*ELECTRIC SHALL BE WATERPROOFED TO DFE.
*FINAL ELEVATION CERTIFICATE REQUIRED PRIOR TO FINAL INSPECTION.
****STAFF***
NEEDS DEVELOPMENT PERMIT # AND FEE
|
7/22/2024
|
Final Review - Processing
ZONING: ACCESSORY BUILDING. EC
*ELECTRIC SHALL BE WATERPROOFED TO DFE.
*FINAL ELEVATION CERTIFICATE REQUIRED PRIOR TO FINAL INSPECTION.
****STAFF***
NEEDS DEVELOPMENT PERMIT # AND FEE
|
7/22/2024
|
Final Review - Payment Needed
ZONING: ACCESSORY BUILDING. EC
*ELECTRIC SHALL BE WATERPROOFED TO DFE.
*FINAL ELEVATION CERTIFICATE REQUIRED PRIOR TO FINAL INSPECTION.
****STAFF***
NEEDS DEVELOPMENT PERMIT # AND FEE
|
7/22/2024
|
Permit Issued
Permit # created and approved from payment.
|
1/9/2025
|
Point Review - Reviewed
ZONING: ACCESSORY BUILDING. EC
*ELECTRIC SHALL BE WATERPROOFED TO DFE.
*FINAL ELEVATION CERTIFICATE REQUIRED PRIOR TO FINAL INSPECTION.
****STAFF***
NEEDS DEVELOPMENT PERMIT # AND FEE
|