5/12/2023
|
Application pending.
|
6/15/2023
|
Plan Review - Documents Required
NEEDED:
*OWNERS PHONE NUMBER
*CONSTRUCTION DETAILS SECTION COMPLETED
*SEALED ARCHITECT/ENGINEER PLANS
*ENERGY CODE & MANUAL J FORMS
*OWNER AND CONTRACTOR SIGNATURE PAGE
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
*TRUSS ENGINEERING
***PRIOR TO INSPECTIONS***
RECORDED NOC
|
6/20/2023
|
Plan Review - Documents Required
NEEDED:
*OWNERS PHONE NUMBER
*CONSTRUCTION DETAILS SECTION COMPLETED
*SEALED ARCHITECT/ENGINEER PLANS
*ENERGY CODE & MANUAL J FORMS
*OWNER AND CONTRACTOR SIGNATURE PAGE
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
*TRUSS ENGINEERING
***PRIOR TO INSPECTIONS***
RECORDED NOC
|
6/26/2023
|
Plan Review - Corrections Needed
NEEDED:
**manual j has no equipment listed, manual j must comply with seer2
*SEALED ARCHITECT/ENGINEER PLANS
*ENERGY CODE FORMS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
7/3/2023
|
Plan Review - Corrections Needed
NEEDED:
**MANUAL J HAS NO EQUIPMENT LISTED, MANUAL J MUST COMPLY WITH SEER2
*SEALED ARCHITECT/ENGINEER PLANS
*ENERGY CODE FORMS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
7/10/2023
|
Plan Review - On Hold-Incomplete
NEEDED:
**MANUAL J HAS NO EQUIPMENT LISTED, MANUAL J MUST COMPLY WITH SEER2
*SEALED ARCHITECT/ENGINEER PLANS
*ENERGY CODE FORMS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
7/17/2023
|
Plan Review - On Hold-Incomplete
NEEDED:
**MANUAL J HAS NO EQUIPMENT LISTED, MANUAL J MUST COMPLY WITH SEER2
*SEALED ARCHITECT/ENGINEER PLANS
*ENERGY CODE FORMS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
7/24/2023
|
Plan Review - On Hold-Incomplete
NEEDED:
**MANUAL J HAS NO EQUIPMENT LISTED, MANUAL J MUST COMPLY WITH SEER2
*SEALED ARCHITECT/ENGINEER PLANS
*ENERGY CODE FORMS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
7/25/2023
|
Plan Review - On Hold-Incomplete
NEEDED:
**MANUAL J HAS NO EQUIPMENT LISTED, MANUAL J MUST COMPLY WITH SEER2 (NEED BY FINAL REVIEW)
*SEALED ARCHITECT/ENGINEER PLANS
*ENERGY CODE FORMS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
7/31/2023
|
Plan Review - On Hold-Incomplete
NEEDED:
**MANUAL J HAS NO EQUIPMENT LISTED, MANUAL J MUST COMPLY WITH SEER2, SQFT ON MANUAL J IS 1062SQFT HOUSE IS 1428SQFT (NEED BY FINAL REVIEW)
*SEALED ARCHITECT/ENGINEER PLANS
*ENERGY CODE FORMS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
8/9/2023
|
Plan Review - On Hold-Incomplete
NEEDED:
**MANUAL J HAS NO EQUIPMENT LISTED, MANUAL J MUST COMPLY WITH SEER2, SQFT ON MANUAL J IS 1062SQFT HOUSE IS 1428SQFT (NEED BY FINAL REVIEW)
*SEALED ARCHITECT/ENGINEER PLANS
*ENERGY CODE FORMS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
8/14/2023
|
Plan Review - On Hold-Incomplete
NEEDED:
**MANUAL J HAS NO EQUIPMENT LISTED, MANUAL J MUST COMPLY WITH SEER2, SQFT ON MANUAL J IS 1062SQFT HOUSE IS 1428SQFT (NEED BY FINAL REVIEW)
*SEALED ARCHITECT/ENGINEER PLANS
*ENERGY CODE FORMS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
8/28/2023
|
Plan Review - On Hold-Incomplete
NEEDED:
**MANUAL J HAS NO EQUIPMENT LISTED, MANUAL J MUST COMPLY WITH SEER2, SQFT ON MANUAL J IS 1062SQFT HOUSE IS 1428SQFT (NEED BY FINAL REVIEW)
*SEALED ARCHITECT/ENGINEER PLANS
*ENERGY CODE FORMS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
9/5/2023
|
Plan Review - On Hold-Incomplete
NEEDED:
**MANUAL J HAS NO EQUIPMENT LISTED, MANUAL J MUST COMPLY WITH SEER2, SQFT ON MANUAL J IS 1062SQFT HOUSE IS 1428SQFT (NEED BY FINAL REVIEW)
*SEALED ARCHITECT/ENGINEER PLANS
*ENERGY CODE FORMS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
9/11/2023
|
Plan Review - On Hold-Incomplete
NEEDED:
**MANUAL J HAS NO EQUIPMENT LISTED, MANUAL J MUST COMPLY WITH SEER2, SQFT ON MANUAL J IS 1062SQFT HOUSE IS 1428SQFT (NEED BY FINAL REVIEW)
*SEALED ARCHITECT/ENGINEER PLANS
*ENERGY CODE FORMS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
9/18/2023
|
Plan Review - On Hold-Incomplete
NEEDED:
**MANUAL J HAS NO EQUIPMENT LISTED, MANUAL J MUST COMPLY WITH SEER2, SQFT ON MANUAL J IS 1062SQFT HOUSE IS 1428SQFT (NEED BY FINAL REVIEW)
*SEALED ARCHITECT/ENGINEER PLANS
*ENERGY CODE FORMS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
9/25/2023
|
Plan Review - On Hold-Incomplete
NEEDED:
**MANUAL J HAS NO EQUIPMENT LISTED, MANUAL J MUST COMPLY WITH SEER2, SQFT ON MANUAL J IS 1062SQFT HOUSE IS 1428SQFT (NEED BY FINAL REVIEW)
*SEALED ARCHITECT/ENGINEER PLANS
*ENERGY CODE FORMS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
10/2/2023
|
Plan Review - On Hold-Incomplete
NEEDED:
**MANUAL J HAS NO EQUIPMENT LISTED, MANUAL J MUST COMPLY WITH SEER2, SQFT ON MANUAL J IS 1062SQFT HOUSE IS 1428SQFT (NEED BY FINAL REVIEW)
*SEALED ARCHITECT/ENGINEER PLANS
*ENERGY CODE FORMS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
10/11/2023
|
Plan Review - On Hold-Incomplete
NEEDED:
**MANUAL J HAS NO EQUIPMENT LISTED, MANUAL J MUST COMPLY WITH SEER2, SQFT ON MANUAL J IS 1062SQFT HOUSE IS 1428SQFT (NEED BY FINAL REVIEW)
*SEALED ARCHITECT/ENGINEER PLANS
*ENERGY CODE FORMS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
10/16/2023
|
Plan Review - On Hold-Incomplete
NEEDED:
*SEALED ARCHITECT/ENGINEER PLANS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
10/23/2023
|
Plan Review - On Hold-Incomplete
NEEDED:
*SEALED ARCHITECT/ENGINEER PLANS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
10/30/2023
|
Plan Review - On Hold-Incomplete
NEEDED:
*SEALED ARCHITECT/ENGINEER PLANS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
11/6/2023
|
Plan Review - On Hold-Incomplete
NEEDED:
*SEALED ARCHITECT/ENGINEER PLANS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
11/13/2023
|
Plan Review - On Hold-Incomplete
NEEDED:
*SEALED ARCHITECT/ENGINEER PLANS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
11/20/2023
|
Plan Review - On Hold-Incomplete
NEEDED:
*SEALED ARCHITECT/ENGINEER PLANS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
11/27/2023
|
Plan Review - On Hold-Incomplete
NEEDED:
*SEALED ARCHITECT/ENGINEER PLANS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
12/6/2023
|
Plan Review - On Hold-Incomplete
NEEDED:
*SEALED ARCHITECT/ENGINEER PLANS
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
12/7/2023
|
Point Review - Printed-Online Application
NEEDED:
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
12/7/2023
|
Point Review - Reviewed
NEEDED:
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
12/7/2023
|
Plan Review - Building Approved
NEEDED:
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
12/7/2023
|
Plan Review - Electrical Approved
NEEDED:
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
12/7/2023
|
Plan Review - Mechanical Approved
NEEDED:
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
12/7/2023
|
Plan Review - Plumbing Approved
NEEDED:
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
12/7/2023
|
Plan Review - Fuel/Gas Approved
NEEDED:
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
12/7/2023
|
Plan Review - Reviewed
NEEDED:
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
12/12/2023
|
Zoning Review - Reviewed
NEEDED:
*ENV HEALTH SIGNED SITE PLAN APPROVAL-- CONTACT 386-758-1058
|
12/13/2023
|
Final Review - Payment Needed
|
12/21/2023
|
Permit Issued
Permit #000048894 created and approved.
|