Columbia County is committed to ensuring accessibility to this website regardless of disability. If anyone encounters a feature on this website that is inaccessible due to a disability, please contact the County Manger’s Office and the Columbia County Board of County Commissioners at (386) 758-1005. You may also email that office at patrick_weaver@columbiacountyfla.com and provide a brief description of the inaccessible feature. The County will either correct the inaccessible feature or, if correction is not possible due to technical limitations, provide the desired information through alternative means.

Skip to content

Columbia County, FL | Permit Details

Electrical Service Permit
Address 196 SW PHEASANT WAY
LAKE CITY, FL 32024
Parcel #: 03023-121
Acres: 0.50
Owner: Bostic Mary L,
Subdivision: Callaway Phase 1
Zoning: RSF-2
Flood Zone: X
District: 3
Application #: 63442
Permit #: 000048736
Related Permit:
Submitted: Monday, November 27, 2023
Issued: Monday, November 27, 2023
Expires: Tuesday, December 19, 2023
Completed: Tuesday, December 19, 2023
Status: Completed
Septic Release? Yes
Notes:

LAKE CITY UTLITY CUSTOMER SERVICE NOTES Locates must be obtained to ensure that the existing utility infrastructure is not damaged or obstructed.
Job Details
Residential or Commercial? Residential
Is the power service? Generator Install
What is the power service for? Existing Site Built Home
Other job details: METER PULL AND GENERATOR INSTALL
Meter or Account: Meter
Meter or Account #: 156216461
Septic # (00-0000) or (X00-000) x23
Electrical Code Edition 2020 National Electrical Code
Fema map number 12023C0289D
Review Notes
11/27/2023 Application pending.
11/27/2023 Application submitted by applicant.
11/27/2023 City of Lake City Utilities Notified City of Lake City Notified of Application within Utility Service Areas LC_WATER,.
11/27/2023 Final Review - Payment Needed
11/27/2023 Permit Issued Permit # created and approved from payment.
Contractors
Name/ Business License Title Role
Marcus Matthews
Matthews Electric Llc
EC13005459 Electrical Contractor Contractor
Inspections
Inspection Notes Performed By Date
Cancelled: Electrical - Reconnect Service Final Melissa Garber 12/8/2023
Failed: Electrical - Generator Final Neutrals And Grounds Not Separated Matt Forsyth 12/8/2023
Failed: Electrical - Generator Final No Access, Neutral Not Insulated Anthony Aslan 12/13/2023
Passed: Electrical - Generator Final Added Insulated Ground And Neutral Wire To Existing Three Wire System Troy Crews 12/19/2023
Release to power company Troy Crews 12/19/2023