Columbia County is committed to ensuring accessibility to this website regardless of disability. If anyone encounters a feature on this website that is inaccessible due to a disability, please contact the County Manger’s Office and the Columbia County Board of County Commissioners at (386) 758-1005. You may also email that office at patrick_weaver@columbiacountyfla.com and provide a brief description of the inaccessible feature. The County will either correct the inaccessible feature or, if correction is not possible due to technical limitations, provide the desired information through alternative means.

Skip to content

Columbia County, FL | Permit Details

Electrical Service Permit

Address 3172 SW HERLONG ST
FORT WHITE, FL 32038
Parcel #: 03816-202
Acres: 4.99
Owner: Medlin Justine D
Subdivision: Crossroads Unr
Zoning: A-3
Flood Zone: X
District: 4
Application #: 62602
Permit #: 000048145
Related Permit:
Submitted: Thursday, September 14, 2023
Issued: Friday, September 15, 2023
Expires: Thursday, November 30, 2023
Completed: Thursday, November 30, 2023
Status: Completed
Septic Release? Yes
Notes:

Job Details
Finished floor requirement
Fema map number 12023C0485C
What is the power service for? Other
Power Company Clay Electric
Septic # (00-0000) or (X00-000) x23
Electrical Code Edition 2017 National Electrical Code
Number of requested AMPS for electrical service: 200
Is the power service? Generator Install
Residential or Commercial? Residential
Review Notes
9/14/2023 Application pending.
9/14/2023 Application submitted by applicant.
9/14/2023 Final Review - Payment Needed
9/14/2023 Final Review - Payment Needed PLEASE EMAIL BLDGINFO@COLUMBIACOUNTY WITH OWNERS PHONE NUMBER
9/15/2023 Permit Issued Permit # created and approved from payment.
Contractors
Name/ Business License Title Role
Christopher J Shea
Trademark Electric Inc
EC13004066 Electrical Contractor Contractor
Inspections
Inspection Notes Performed By Date
Failed: Electrical - Generator Final 1. Need Anti-oxidant Compound On All Aluminum Wires, 2. The Origin Service Disconnect Door Will Not Close And The Dead Front Inside The Disconnect Is Not Fitting Properly. The Splice Blocks Used Inside The Disconnect Are Keeping Dead Front From Closing Properly Which Leaves Gaps Around Breakers Enough To Get A Person Fingers Into Live Parts Gary Pitzer 11/22/2023
Passed: Electrical - Generator Final Per Photo On File Gary Pitzer 11/30/2023
Release to power company Gary Pitzer 11/30/2023