Columbia County is committed to ensuring accessibility to this website regardless of disability. If anyone encounters a feature on this website that is inaccessible due to a disability, please contact the County Manger’s Office and the Columbia County Board of County Commissioners at (386) 758-1005. You may also email that office at patrick_weaver@columbiacountyfla.com and provide a brief description of the inaccessible feature. The County will either correct the inaccessible feature or, if correction is not possible due to technical limitations, provide the desired information through alternative means.

Skip to content

Columbia County, FL | Permit Details

Additions Permit
Address 340 NW COMMERCE DR
LAKE CITY, FL 32055
Parcel #: 02556-003
Acres: 41.25
Owner: Notami Hospitals Of Fl Inc
Subdivision:
Zoning:
Flood Zone: X
District: 3
Application #: 53804
Permit #: 000044176
Related Permit:
Submitted: Friday, March 4, 2022
Issued: Thursday, April 14, 2022
Expires: Tuesday, February 4, 2025
Completed: Tuesday, February 4, 2025
Status: Completed
Septic Release? Yes
Notes:
ZONING APPROVED BY CITY
Job Details
Is this an addition for commercial or residential use? Commercial
Description of addition: Work of the project includes addition/reno to existing ED, Pharmacy/Dietary Renovation & new Helipad.
Total Estimated Cost 14400000
Heated Area (Sqft) 14779
Total Area (Sqft) 14779
Stories 1
Building Height 16
Select driveway access to property: Existing Drive
Fire sprinklers? Yes
Building Code Occupancy Types Assembly
Occupancy Use Title hospital
Setbacks Front 20'
Setback Side 1 10'
Setback Side 2 10'
Setback Rear 15'
Septic# (00-0000) or (X00-000) x-city
Service Amps 2266.33
Dev Permit # F023-
Building Code Edition 2020 Florida Building Code 7th Edition and 2017 National Electrical Code
Fema map number 12023C0291D
Sealed roof decking options. (Must select one.) Other (explain)
Sealed roof decking explanation for other option. Please refer to attached construction documents.
Review Notes
3/3/2022 Application pending.
3/4/2022 City of Lake City City of Lake City Notified of Application within Utility Service Areas LC_GAS, LC_WATER, LC_SEWER.
3/11/2022 Plan Review - Documents Required NEEDED: *CGC TO COMPLETE CONTRACTOR REGISTRATION *SIGNED SUB VF FORM-- ALL CONTRACTORS MUST REGISTER IF NOT ALREADY *NEED EST COST BROKEN INTO ELECTRICAL, PLUMBING, AND MECHANICAL *COMPLETED COMMERCIAL CHECKLIST *APPROVAL ALLOWING JILL ADAMS TO SIGN AS OWNER *SITE PLAN SHOWING DIMENSIONS FROM PROPERTY LINES TO STRUCTURE/ADDITION PLANS (SEALED) ENERGY CALCULATIONS **PRIOR TO INSPECTIONS*** RECORDED NOC
3/18/2022 Point Review - Documents Required NEEDED: *CGC TO COMPLETE CONTRACTOR REGISTRATION *SIGNED SUB VF FORM-- ALL CONTRACTORS MUST REGISTER IF NOT ALREADY *NEED EST COST BROKEN INTO ELECTRICAL, PLUMBING, AND MECHANICAL *COMPLETED COMMERCIAL CHECKLIST *APPROVAL ALLOWING JILL ADAMS TO SIGN AS OWNER *SITE PLAN SHOWING DIMENSIONS FROM PROPERTY LINES TO STRUCTURE/ADDITION PLANS (SEALED) ENERGY CALCULATIONS **PRIOR TO INSPECTIONS*** RECORDED NOC
3/18/2022 Plan Review - Documents Required NEEDED: *CGC TO COMPLETE CONTRACTOR REGISTRATION *SIGNED SUB VF FORM-- ALL CONTRACTORS MUST REGISTER IF NOT ALREADY *NEED EST COST BROKEN INTO ELECTRICAL, PLUMBING, AND MECHANICAL *COMPLETED COMMERCIAL CHECKLIST *APPROVAL ALLOWING JILL ADAMS TO SIGN AS OWNER *SITE PLAN SHOWING DIMENSIONS FROM PROPERTY LINES TO STRUCTURE/ADDITION PLANS (SEALED) ENERGY CALCULATIONS **PRIOR TO INSPECTIONS*** RECORDED NOC
3/21/2022 Plan Review - Documents Required NEEDED: *CITY UTILITY AVAILABILITY LETTER *ALL CONTRACTORS MUST REGISTER--- CGC, SEAY, WYNKOOP, AND FURLONG MUST COMPLETE REGISTRATION--- WYNKOOP MUST HOLD A CCC LICENSE TO COMPLETE ROOF *NEED EST COST BROKEN INTO ELECTRICAL, PLUMBING, AND MECHANICAL *ELECTRICAL AMPS NEED MECHANICAL, ELECTRICAL, AND PLUMBING PLANS **PRIOR TO INSPECTIONS*** RECORDED NOC
3/23/2022 Plan Review - Documents Required NEEDED: *CITY UTILITY AVAILABILITY LETTER *ALL CONTRACTORS MUST REGISTER--- CGC, SEAY, WYNKOOP, AND FURLONG MUST COMPLETE REGISTRATION--- WYNKOOP MUST HOLD A CCC LICENSE TO COMPLETE ROOF *NEED EST COST BROKEN INTO ELECTRICAL, PLUMBING, AND MECHANICAL *ELECTRICAL AMPS *NEED MECHANICAL, ELECTRICAL, AND PLUMBING PLANS NEED ACTUAL FLORIDA PRODUCT APPROVAL NUMBERS FOE EXTERIOR DOOR, WINDOWS, ROOFING ON COLUMBIA COUNTY FORM
3/24/2022 Plan Review - Documents Required NEEDED: *CITY UTILITY AVAILABILITY LETTER *ALL CONTRACTORS MUST REGISTER--- SEAY AND FURLONG MUST COMPLETE REGISTRATION--OTT REGISTERED CGC LICENSE, WE MUST HAVE A CCC LICENSE FOR ROOFING *ELECTRICAL AMPS *NEED MECHANICAL, ELECTRICAL, AND PLUMBING PLANS *NEED ACTUAL FLORIDA PRODUCT APPROVAL NUMBERS FOE EXTERIOR DOOR, WINDOWS, ROOFING ON COLUMBIA COUNTY FORM
3/24/2022 Point Review - Reviewed NEEDED: *CITY UTILITY AVAILABILITY LETTER *ALL CONTRACTORS MUST REGISTER--- SEAY IS THE ONLY ONE LEFT
3/24/2022 Final Review - Documents Required NEEDED: *CITY UTILITY AVAILABILITY LETTER *ALL CONTRACTORS MUST REGISTER--- SEAY IS THE ONLY ONE LEFT
3/25/2022 Plan Review - Plumbing Approved NEEDED: *CITY UTILITY AVAILABILITY LETTER *ALL CONTRACTORS MUST REGISTER--- SEAY IS THE ONLY ONE LEFT
3/25/2022 Plan Review - Mechanical Approved NEEDED: *CITY UTILITY AVAILABILITY LETTER *ALL CONTRACTORS MUST REGISTER--- SEAY IS THE ONLY ONE LEFT
3/25/2022 Plan Review - Electrical Approved NEEDED: *CITY UTILITY AVAILABILITY LETTER *ALL CONTRACTORS MUST REGISTER--- SEAY IS THE ONLY ONE LEFT
3/25/2022 Plan Review - Building Approved NEEDED: *CITY UTILITY AVAILABILITY LETTER *ALL CONTRACTORS MUST REGISTER--- SEAY IS THE ONLY ONE LEFT
3/25/2022 Plan Review - Reviewed NEEDED: *CITY UTILITY AVAILABILITY LETTER *ALL CONTRACTORS MUST REGISTER--- SEAY IS THE ONLY ONE LEFT
3/25/2022 Zoning Review - Reviewed NEEDED: *CITY UTILITY AVAILABILITY LETTER *ALL CONTRACTORS MUST REGISTER--- SEAY IS THE ONLY ONE LEFT
3/25/2022 Final Review - Documents Required NEEDED: *CITY UTILITY AVAILABILITY LETTER *ALL CONTRACTORS MUST REGISTER--- SEAY IS THE ONLY ONE LEFT
3/25/2022 Final Review - Documents Required NEEDED: *CITY UTILITY AVAILABILITY LETTER
3/28/2022 Final Review - Documents Required NEEDED: *CITY UTILITY AVAILABILITY LETTER
3/29/2022 Final Review - Documents Required NEEDED: *CITY UTILITY AVAILABILITY LETTER
4/4/2022 Final Review - Payment Needed
4/14/2022 Permit Issued Permit #000044176 created and approved.
Contractors
Name/ Business License Title Role
Thomas Smith
W.w. Gay Mechanical Contractor Of Gainesville Inc
CMC1249841 Mechanical Contractor Subcontractor
Thomas Smith
W.w. Gay Mechanical Contractor Of Gainesville Inc
County License & State License Expired.
CFC1425962 Plumbing Contractor Subcontractor
Robert Gambrell
Robins & Morton
County License & State License & Liability Insurance & Workers Comp Expired.
CGC057104 Cert. General Contractor
Jonathan Belcher
Marion Service Roofing & Sheet Metal Co
County License & State License & Liability Insurance & Workers Comp Expired.
CCC1328582 Cert. Roofing Subcontractor
James B Seay
Miller Electric Company
County License & State License & Liability Insurance & Workers Comp Expired.
EC13003061 Cert. Electrical Contractor
Richard Bloom
W W Gay Gay Fire Protection, Inc.
County License & State License & Liability Insurance & Workers Comp & Employees Workers Comp Expired.
421788-0001-2001 Cert. Fire/water System Subcontractor
Inspections
Inspection Notes Performed By Date
Passed: Plumbing/Gas - 1st Underground Rough–In West Half First Rough E.r. Addition Troy Crews 8/11/2022
Passed: Plumbing/Gas - 1st Underground Rough–In North End Rough In Sanitary And Storm Troy Crews 8/25/2022
Failed: Building - Slab Already Poured, Need Third Party Inspection Report And Pictures If Available Troy Crews 8/31/2022
Cancelled: Plumbing/Gas - Rain Leader Melissa Garber 9/7/2022
Cancelled: Plumbing/Gas - Rain Leader Troy Crews 9/8/2022
Passed: Building - Slab N Half Emergency Room Addition Troy Crews 9/12/2022
Passed: Building - Slab Penthouse Slab At Emergency Room Job Troy Crews 9/20/2022
Passed: Building - Framing South Wall And Partial North Wall. Troy Crews 10/7/2022
Passed: Building - Framing Remainder Exterior Walls Er Area. Troy Crews 10/12/2022
Passed: Building - Framing Remainder Exterior Walls Er. Troy Crews 10/18/2022
Passed: Building - Wall Sheathing Troy Crews 10/18/2022
Passed: Building - Framing Partial For Top Four Feet Of Walls Troy Crews 10/21/2022
Failed: Fire - Fire Rated Wall Several Locations Where Coating Had Been Compromised Due To Clamps And Damage. Two I Beams That Were Installed Due To A Damaged I Beam Had No Coating At All. Told The Superintendent To Call For Reinspection Once Everything Was Ready. Dwight Boozer 10/21/2022
Passed: Building - Wall Sheathing Remainder Exterior Sheathing, Exterior Insulation, And Window Sill Mounting. Troy Crews 10/25/2022
Passed: Plumbing/Gas - Water Pipe Eastside Of Er Area Troy Crews 10/28/2022
Passed: Building - Framing Window Frames Installed In Jam Troy Crews 10/28/2022
Passed: Building - Rated Assembly Fastening Troy Crews 10/28/2022
Passed: Plumbing/Gas - Rain Leader Troy Crews 10/28/2022
Passed: Building - Ext Strapping/Wall Sheathing Troy Crews 11/1/2022
Passed: Building - Framing Partial Interior Middle Troy Crews 11/15/2022
Passed: Electrical - 2nd Rough-In Partial Interior Middle Troy Crews 11/15/2022
Passed: Mechanical - Rough In Partial Troy Crews 11/15/2022
Passed: Plumbing/Gas - Sanitary Interior Middle Pressure On Water And Waste Lines Test. Troy Crews 11/15/2022
Passed: Plumbing/Gas - 2nd Rough-In Partial Troy Crews 11/15/2022
Passed: Mechanical - Framing/Fire Damper All Fire Dampers Not Fire Smoke Activated Observed In Closed Position To Confirm No Obstruction. Troy Crews 11/16/2022
Passed: Electrical - 2nd Rough-In Partial Troy Crews 12/12/2022
Passed: Plumbing/Gas - Sanitary Reminder Of Sanitary Top Out Troy Crews 12/12/2022
Passed: Plumbing/Gas - Water Pipe Remainder Of Potable Water Piping Test Troy Crews 12/12/2022
Passed: Plumbing/Gas - 2nd Rough-In Troy Crews 12/12/2022
Passed: Plumbing/Gas - Medical Gas 150 Psi Test All 3 Lines. Troy Crews 12/12/2022
Passed: Mechanical - Pipe Pressure Test 150 Psi Hot Water Lines For Vav Troy Crews 12/15/2022
Passed: Building - Framing Approved As Requested Troy Crews 12/28/2022
Passed: Building - Fire Rated Wall Approved As Requested Troy Crews 12/28/2022
Passed: Electrical - 2nd Rough-In Troy Crews 12/28/2022
Passed: Building - Framing Front Canopy Troy Crews 1/17/2023
Passed: Electrical - Above Ceiling Front Canopy Troy Crews 1/17/2023
Passed: Plumbing/Gas - Rain Leader Front Canopy Troy Crews 1/17/2023
Failed: Building - Fire Rated Wall Not Complete, Need Fire Caulking And Electrical Complete. Troy Crews 3/22/2023
Failed: Electrical - Above Ceiling Not Complete. Troy Crews 3/28/2023
Passed: Electrical - Above Ceiling Troy Crews 3/31/2023
Passed: Fire - Fire Final Dwight Boozer 4/19/2023
Passed: Building - Final Area A Phase 1 A, And 1 B Troy Crews 4/19/2023
Passed: Plumbing/Gas - 1st Underground Rough–In Partial Waste Lines Troy Crews 7/6/2023
Passed: Plumbing/Gas - 2nd Rough-In Troy Crews 7/11/2023
Passed: Building - Framing Troy Crews 7/14/2023
Passed: Building - Framing Send Me Pictures Of Pressure Test On Last Two Plumbing Lines. Troy Crews 7/18/2023
Passed: Plumbing/Gas - 2nd Rough-In Troy Crews 8/3/2023
Passed: Building - Fire Rated Wall Partial Troy Crews 8/18/2023
Passed: Electrical - Above Ceiling Troy Crews 8/22/2023
Passed: Fire - Fire Rated Wall Labels Have Been Installed Troy Crews 8/22/2023
Rescheduled 8/28/2023:Building - Final Troy Crews 8/28/2023
Passed: Building - Final Troy Crews 8/28/2023
Passed: Building - Framing Partial West End Pharmacy Troy Crews 9/7/2023
Passed: Building - Insulation West End Troy Crews 9/7/2023
Passed: Electrical - 2nd Rough-In Partial Troy Crews 9/15/2023
Passed: Plumbing/Gas - 2nd Rough-In 2 Sink Areas In Wall Only Troy Crews 9/15/2023
Passed: Plumbing/Gas - 1st Underground Rough–In Tie In Two Sinks To Existing Sanitary Troy Crews 9/25/2023
Passed: Building - Ext Strapping/Wall Sheathing Troy Crews 10/3/2023
Passed: Electrical - 2nd Rough-In Troy Crews 10/3/2023
Passed: Plumbing/Gas - Water Pipe Troy Crews 10/11/2023
Passed: Electrical - Above Ceiling Troy Crews 10/25/2023
Passed: Plumbing/Gas - Water Pipe Troy Crews 10/25/2023
Passed: Electrical - Above Ceiling Troy Crews 11/9/2023
Passed: Fire - Fire Rated Wall Troy Crews 11/9/2023
Passed: Plumbing/Gas - Water Pipe Troy Crews 11/9/2023
Passed: Building - Final Pharmacy Phase Troy Crews 12/4/2023
Cancelled: Plumbing/Gas - Rain Leader Troy Crews 2/1/2024
Passed: Plumbing/Gas - 1st Underground Rough–In Grease Floor Drains Troy Crews 2/1/2024
Passed: Plumbing/Gas - 1st Underground Rough–In Vent Lines Troy Crews 2/5/2024
Passed: Building - Framing Troy Crews 2/14/2024
Passed: Mechanical - Rough In Partial Troy Crews 2/14/2024
Passed: Plumbing/Gas - 2nd Rough-In 2 Nd Rough Walls West Side Of Area Troy Crews 2/14/2024
Passed: Building - Framing Troy Crews 2/16/2024
Passed: Electrical - 2nd Rough-In Troy Crews 2/16/2024
Passed: Building - Insulation Troy Crews 2/16/2024
Passed: Building - Strapping Troy Crews 2/16/2024
Passed: Plumbing/Gas - Sanitary Troy Crews 2/16/2024
Passed: Plumbing/Gas - Water Pipe Troy Crews 2/16/2024
Passed: Plumbing/Gas - 2nd Rough-In Troy Crews 2/16/2024
Passed: Mechanical - Rough In Troy Crews 2/21/2024
Passed: Plumbing/Gas - Sanitary Troy Crews 2/21/2024
Passed: Plumbing/Gas - Water Pipe Troy Crews 2/21/2024
Passed: Fire - Fire Rated Wall Joshua Wehinger 2/26/2024
Rescheduled 2/27/2024:Fire - Sprinkler System Alteration Troy Crews 2/27/2024
Passed: Fire - Fire Rated Wall Joshua Wehinger 2/28/2024
Rescheduled 2/28/2024:Fire - Sprinkler System Alteration Troy Crews 2/28/2024
Passed: Fire - Sprinkler System Alteration Joshua Wehinger 2/29/2024
Passed: Electrical - Above Ceiling Troy Crews 2/29/2024
Passed: Mechanical - Rough In Troy Crews 2/29/2024
Passed: Plumbing/Gas - 1st Underground Rough–In Troy Crews 3/7/2024
Rescheduled 3/14/2024:Plumbing/Gas - 1st Underground Rough–In Troy Crews 3/13/2024
Rescheduled 3/14/2024:Plumbing/Gas - Interceptor Troy Crews 3/13/2024
Rescheduled 3/15/2024:Plumbing/Gas - 1st Underground Rough–In Troy Crews 3/14/2024
Rescheduled 3/15/2024:Plumbing/Gas - Interceptor Troy Crews 3/14/2024
Passed: Building - Fire Rated Wall Troy Crews 3/14/2024
Passed: Electrical - Above Ceiling Troy Crews 3/14/2024
Passed: Mechanical - Rough In Troy Crews 3/14/2024
Passed: Plumbing/Gas - 2nd Rough-In Troy Crews 3/14/2024
Passed: Plumbing/Gas - 1st Underground Rough–In Troy Crews 3/15/2024
Passed: Plumbing/Gas - Interceptor Troy Crews 3/15/2024
Passed: Plumbing/Gas - Interceptor Mai Grease Trap Outside Anchored Down Troy Crews 3/18/2024
Passed: Fire - Fire Final Joshua Wehinger 3/26/2024
Passed: Building - Final Dishwash Area And Dining Area Troy Crews 3/26/2024
Passed: Fire - Fire Final Joshua Wehinger 3/29/2024
Passed: Plumbing/Gas - 1st Underground Rough–In Outlet Troy Crews 4/19/2024
Passed: Building - Framing Troy Crews 5/9/2024
Passed: Plumbing/Gas - 1st Underground Rough–In Partial On Main Grease Trap Line Kitchen Area Troy Crews 5/21/2024
Passed: Plumbing/Gas - Sanitary Troy Crews 5/21/2024
Passed: Plumbing/Gas - 1st Underground Rough–In Partial Kit Hen Area Troy Crews 5/29/2024
Passed: Building - Framing Area To South Troy Crews 6/5/2024
Passed: Electrical - 1st Underground Rough–In Troy Crews 6/5/2024
Passed: Plumbing/Gas - 1st Underground Rough–In Partial South Area Troy Crews 6/5/2024
Passed: Plumbing/Gas - 1st Underground Rough–In Remainder Kitchen Area Troy Crews 6/12/2024
Passed: Plumbing/Gas - Sanitary Troy Crews 6/12/2024
Passed: Building - Framing New Kitchen Area Walls Troy Crews 6/26/2024
Passed: Building - Fire Rated Wall Shaft Wall Installed Cooler Area Troy Crews 6/26/2024
Passed: Electrical - 2nd Rough-In Troy Crews 6/26/2024
Passed: Mechanical - Kitchen Hood Partial Hoods All Thread Hangars Troy Crews 6/26/2024
Passed: Plumbing/Gas - Water Pipe Troy Crews 6/26/2024
Passed: Plumbing/Gas - 2nd Rough-In Troy Crews 6/26/2024
Passed: Fire - Kitchen Hood – Fire Suppression Test Joshua Wehinger 6/26/2024
Passed: Plumbing/Gas - Sanitary Grease Line Around Storm Manhole To New Grease Interceptor. Troy Crews 6/28/2024
Passed: Electrical - Above Ceiling Pictures Sent Troy Crews 7/10/2024
Passed: Plumbing/Gas - Water Pipe Pictures Sent Troy Crews 7/10/2024
Passed: Plumbing/Gas - Water Pipe Pictures Sent Troy Crews 7/15/2024
Passed: Fire - Fire Rated Wall Joshua Wehinger 8/1/2024
Passed: Building - Fire Rated Wall Joshua Wehinger 8/1/2024
Passed: Mechanical - Pipe Pressure Test Kitchen Piping Rough In 100psi Troy Crews 8/15/2024
Passed: Electrical - Above Ceiling Troy Crews 9/4/2024
Passed: Building - Final Phase 6 Partial Kitchen Area Troy Crews 9/11/2024
Passed: Plumbing/Gas - 1st Underground Rough–In 7th Phase Kitchen Area Troy Crews 11/21/2024
Passed: Building - Framing Kitchen Area Phase 7 Troy Crews 12/5/2024
Passed: Electrical - 2nd Rough-In Phase 7 Troy Crews 12/5/2024
Passed: Plumbing/Gas - 2nd Rough-In Phase 7 Troy Crews 12/5/2024
Passed: Mechanical - Pipe Pressure Test Troy Crews 12/11/2024
Passed: Plumbing/Gas - Sanitary Troy Crews 12/11/2024
Passed: Plumbing/Gas - Water Pipe Troy Crews 12/11/2024
Passed: Electrical - Above Ceiling Partial For Border Tiles Troy Crews 1/13/2025
Passed: Electrical - Above Ceiling Troy Crews 1/17/2025
Certificate-Release Certificate All Phases Now Complete Troy Crews 2/4/2025
Passed: Building - Final Troy Crews 2/4/2025
(Requested) Fire-Aboveground Sprinkler - Visual (On Site)
(Requested) Mechanical-Kitchen Hood
(Requested) Plumbing/Gas-Sanitary
(Requested) Plumbing/Gas-Water Pipe
(Requested) Plumbing/Gas-2nd Rough-In
(Requested) Fire-Sprinkler System Alteration
(Requested) Mechanical-Pipe Pressure Test
(Requested) Fire-Sprinkler System Alteration