Failed: Mechanical - Rough In
Return In Kitchen Is Less Than 10'ft From Stove.
m1602.2return Air Openings.
return Air Openings For Heating, Ventilation And Air Conditioning Systems Shall Comply With All Of The Following:
1.openings Shall Not Be Located Less Than 10 Feet (3048 Mm) Measured In Any Direction From An Open Combustion Chamber Or Draft Hood Of Another Appliance Located In The Same Room Or Space.
2.the Amount Of Return Air Taken From Any Room Or Space Shall Be Not Greater Than The Flow Rate Of Supply Air Delivered To Such Room Or Space.
3.return And Transfer Openings Shall Be Sized In Accordance With The Appliance Or Equipment Manufacturers’ Installation Instructions, Manual D Or The Design Of The Registered Design Professional.
4.return Air Shall Not Be Taken From A Closet, Bathroom, Toilet Room, Kitchen, Garage, Mechanical Room, Boiler Room, Furnace Room Or Unconditioned Attic.
exceptions:
1.taking Return Air From A Kitchen Is Not Prohibited Where Such Return Air Openings Serve The Kitchen Only, And Are Located Not Less Than 10 Feet (3048 Mm) From The Cooking Appliances
Inspected by Anthony Aslan