Electrical Service
Permit
| Application #: | 74286 |
| Permit #: |
000054656 |
| Related Permit: |
|
| Submitted: | Wednesday, December 10, 2025 |
| Issued: | Wednesday, December 10, 2025 |
| Expires: | Tuesday, December 16, 2025 |
| Completed: | Tuesday, December 16, 2025 |
| Status: |
Completed |
| Septic Release? |
Yes |
Job Details
| Finished floor requirement |
|
| Fema map number |
12023C0186D |
| What is the power service for? |
Existing Mobile Home |
| Power Company |
Suwannee Valley Electric |
| Septic # (00-0000) or (X00-000) |
25-0929 |
| Electrical Code Edition |
2020 National Electrical Code |
| Meter or Account: |
Account |
| Meter or Account #: |
814704 |
| Number of requested AMPS for electrical service: |
100 |
| Is the power service? |
Reconnecting Service |
| Residential or Commercial? |
Residential |
Review Notes
| 11/18/2025 |
Application pending. |
| 12/5/2025 |
Application Status Update Notification |
| 12/10/2025 |
Submitted by building department on applicant's behalf |
| 12/10/2025 |
Permit Issued |
Contractors
| Name / Business |
License |
Title |
Role |
Inspections
| Inspection |
Notes |
Performed By |
Date |
| Septic Release Inspection |
|
Health Dept |
12/8/2025 |
| Failed: Electrical - Reconnect Service Final |
1. No Bonding Screw In Main Panel, 2. Service Conductors Cannot Be Reduced By Cutting Of Part Of The Wiring, They Must Be Full Size, 3. Remove The Green Wire Between Meter And Neutral Bar In Main Disconnect (not Needed), 4. Cannot Use Aluminum Wire To And Grounding Electrode, 5. Need Anti-oxidant Compound On All Aluminum Wires |
Gary Pitzer |
12/11/2025 |
| Passed: Electrical - Reconnect Service Final |
Service Only, No Approved To Be Attached To Any Structures On Property |
Gary Pitzer |
12/16/2025 |
| Release to power company |
|
Gary Pitzer |
12/16/2025 |