Permit Details

Permit Search

Permit

Generator

1634 SW SUNVIEW ST
FORT WHITE, FL 32038

Permit #
000054555
Application #
74326
Status Completed
  1. Submitted Nov 20, 2025
  2. Issued Nov 21, 2025
  3. Expires Jun 17, 2026
  4. Completed Dec 19, 2025

Property

Parcel #
03745-214
Owner
Hall Deborah E
Acres
5.00
Subdivision
Sunview Estates
Zoning
ESA-2
Flood zone
X
District
2

Permit

Status
Completed
Septic release
Released
Related permit
—

Job Details

Finished floor requirement
Fema map number
12023C0390C
Residential or Commercial?
Residential
What is the power service for?
Existing Site Built Home
Number of requested AMPS for electrical service:
200
Septic # (00-0000) or (X00-000)
x25
Electrical Code Edition
2020 National Electrical Code

Status & Review History

  1. Application pending.
  2. Application submitted by applicant.
  3. Application Status Update Notification
  4. Permit Issued

Contractors

  • Jack E Phillips

    Security Safe Company

    License
    EC13014598
    Title
    Cert. Electrical
    Role
    Contractor

Inspections

  1. Dec 17, 2025

    Failed: Electrical - Generator Final

    1. All Aluminum Wires Require Anti-oxidant Compound On The Exposed Portion Of Cable After The Removal Of Insulation And Before The Wire Is Installed In The Termination Lugs Of Panels. Some Of The Wiring Involved In This Installation Has No Anti-oxidant Compound And Some Only Have The Compound Spread On Top Of The Lugs, 2. All Unused Openings Including The Dead Front Of Equipment Required Closers, 3. All Wiring Associated With The Installation Shall Be Behind The Dead Front So As Not To Be Using Any Part Of The Dead Front To Hold Wires Into Boxes. Please Reschedule Inspection After Defects Have Been Completed And Let The Home Owner Know The Date We Are To Arrive For Inspection

    Inspected by Gary Pitzer

  2. Dec 19, 2025

    Passed: Electrical - Generator Final

    No Gas Inspection

    Inspected by Gary Pitzer

  3. Dec 19, 2025

    Release to power company

    Inspected by Gary Pitzer