Permit Details

Permit Search

Permit

Electrical Service

851 SW KING ST
LAKE CITY, FL 32024

Permit #
000051936
Application #
68542
Status Completed
  1. Submitted Dec 13, 2024
  2. Issued Dec 27, 2024
  3. Expires Dec 8, 2025
  4. Completed Jun 11, 2025

Property

Parcel #
03193-007
Owner
Wilder Corey, Wilder Brantley
Acres
10.54
Subdivision
—
Zoning
A-3
Flood zone
X
District
5

Permit

Status
Completed
Septic release
Released
Related permit
—

Job Details

Finished floor requirement
Fema map number
12023C0381D
What is the power service for?
Storage Building
Other job details:
Pole Barn
Power Company
Clay Electric
Septic # (00-0000) or (X00-000)
X24-138
Electrical Code Edition
2020 National Electrical Code
Number of requested AMPS for electrical service:
200
Is the power service?
New Power Service
Residential or Commercial?
Residential

Status & Review History

  1. Application pending.
  2. Permit Issued

Contractors

This is an owner-builder project.

Inspections

  1. Dec 27, 2024

    Septic Release Inspection

    Inspected by Health Dept

  2. Jun 9, 2025

    Failed: Electrical - Permanent Power

    Service Requires A Secondary For Of Ground, To Be Spaced At Least 6 Ft Apart With Continuous Ground Wire Between Them, In This Case You Will Need A Secondary Ground Wire To A Second Ground Rod, Also Need To Drive Them To Finish Grade

    Inspected by Gary Pitzer

  3. Jun 10, 2025

    Cancelled: Electrical - Reconnect Service Final

    Inspected by Neonta Anderson

  4. Jun 11, 2025

    Passed: Electrical - Reconnect Service Final

    Service Only

    Inspected by Gary Pitzer