Failed: Building - Final
- Whole House Needs To Be Hot Checked Multiple Gfci Open Grounds, Open Neturals, Circuits Not Hot, Outlet Covers Off.
- No Water On House, No Carpet Installed In Down Stairs Rooms.
- 3 Fixed Pane Windows In Living Room Are Not Tempered Glass
r308.4.3glazing In Windows.
glazing In An Individual Fixed Or Operable Panel That Meets All Of The Following Conditions Shall Be Considered To Be A Hazardous Location:
1.the Exposed Area Of An Individual Pane Is Larger Than 9 Square Feet (0.836 M2),
2.the Bottom Edge Of The Glazing Is Less Than 18 Inches (457 Mm) Above The Floor,
3.the Top Edge Of The Glazing Is More Than 36 Inches (914 Mm) Above The Floor; And
4.one Or More Walking Surfaces Are Within 36 Inches (914 Mm), Measured Horizontally And In A Straight Line, Of The Glazing
-